RFQ Caterpillar 3616 Type V-16 Unused generator sets
Client is interested to purchase 03 units
CATERPILLAR 3616 TYPE V-16 UNUSED GENERATOR SETS or SIMILAR
We need continuous generation of 6 MVA under an N+1 redundancy philosophy. We are talking about critical infrastructure requiring high availability. To cover 6 MVA with redundancy, the most efficient configuration is to use four 2000 kVA units (2 MVA each).
In this way, three units cover the nominal load (3 x 2 = 6 MVA) or equivalent, and the fourth remains in active reserve or to allow for maintenance without affecting operation.
Required Load: 6 MVA (4 units * 2 MW * 0.75) + Backup (1) unit
Installed ISO: N+1
Technical Specifications: 2000 kVA Mobile Power Plant
1. Diesel Engine (Heavy Duty)
Application: Continuous Rating (24/7 Operation)
Configuration: Minimum 16 cylinders in a V configuration, turbocharged and aftercooled.
Displacement: >50 Liters
Fuel Injection System: Electronic (Common Rail or EUI) to optimize fuel consumption and comply with emissions standards (Tier 2 or higher).
Starting: 24V electric starter motor with charging alternator; other starter types are optional.
Filtration: High-efficiency fuel filters with water separator and full-flow oil filters.
2. Alternator (Generator)
Power: 2000 kVA / 1600 kW @ 0.8 PF
Voltage: 480V / 277V (or the required distribution voltage), 3-Phase, 60Hz
Insulation: Class H with protection against saline/humid environments (tropicalized).
Voltage Regulation (AVR): Digital, ±0.5% accuracy.
Excitation: Permanent Magnet (PMG) to withstand load spikes and short circuits.
ATS included (optional)
3. Soundproof Enclosure and Mobility
Soundproofing: 40-foot container-type enclosure (High Cube) with noise attenuation of 75-85 dB(A) at 7 meters.
Construction: Galvanized steel with corrosion-resistant epoxy paint and Class 1 fire-absorbing material.
Trailer: Heavy-duty 3- or 4-axle chassis, ABS braking system, standard lights, and hydraulic or mechanical leveling jacks for stability during operation. Other alternatives are acceptable; this is for reference only.
Accessibility: Wide side doors for major maintenance and integrated access stairs.
4. Control and Synchronization System (Key for N+1)
Controller: Deep Sea 8610 or ComAp InteliGen module (capable of automatic load sharing and synchronization).
Features:
Automatic start/stop based on load demand.
Integrated protections (oil pressure, temperature, overspeed, load failure).
Remote monitoring via Modbus/Ethernet.
Transfer: Motorized power switch (LSIG) integrated into the container. 5. Auxiliary Systems
Fuel Tank: Integrated into the container base (sub-base) with a minimum autonomy of 8-12 hours at full load, with an external filling system.
Cooling: Radiator for ambient temperatures up to 50°C, with a mechanically or electrically driven (VFD) fan.
Exhaust: Critical-type muffler installed internally in the container with a vertical outlet.
Note: Price Exx Work / FOB, destination Venezuela